vix.ing · top · new · best · stats · spec

Mitigation of Datacenter Demand Ramping and Fluctuation using Hybrid ESS and Supercapacitor

2025/12/08 by Ko, Min-Seung, Shim, Jae Woong, Zhu, Hao
Engineering · Materials Science · #Advanced Battery Technologies Research #FOS: Electrical engineering #Microgrid Control and Optimization #Supercapacitor Materials and Fabrication #Systems and Control (eess.SY) #electronic engineering #information engineering

paper · doi:10.48550/arxiv.2512.08076

openalex publication_date 2025/12/08 · openalex created_date 2025/12/11 · openalex updated_date 2026/07/28

Abstract

This paper proposes a hybrid energy storage system (HESS)-based control framework that enables comprehensive power smoothing for hyperscale AI datacenters with large load variations. Datacenters impose severe ramping and fluctuation-induced stresses on the grid frequency and voltage stability. To mitigate such disturbances, the proposed HESS integrates a battery energy storage system (BESS) and a supercapacitor (SC) through coordinated multi-timescale control. A high-pass filter (HPF) separates the datacenter demand into slow and fast components, allocating them respectively to the ESS via a leaky-integral controller and to the SC via a phase-lead proportional-derivative controller enhanced with feedforward and ramp-tracking compensation. Adaptive weighting and repetitive control mechanisms further improve transient and periodic responses. Case studies verify that the proposed method effectively suppresses both ramping and fluctuations, stabilizes the system frequency, and maintains sustainable state-of-charge (SoC) trajectories for both ESS and SC under prolonged, stochastic training cycles.