Design and Testing of an Arc Resistant Power Transformer Tank

2019/06/12 by Samuel Brodeur, Jean-Bernard Dastous, Jean‐Bernard Dastous
Decision Sciences · Engineering · #Electrical Fault Detection and Protection #Power Transformer Diagnostics and Insulation #Risk and Safety Analysis

paper · doi:10.1109/tpwrd.2019.2922505

openalex publication_date 2019/06/12 · openalex created_date 2025/10/10 · openalex updated_date 2026/06/20

Abstract

This paper presents the design and testing of a full-scale 330-kV, 210-MVA transformer tank designed to withstand the pressure effects of a 20 MJ, three-cycle low-impedance fault in oil, and fail at its cover in a safe and controlled manner above that amount of energy. The transformer tank, equipped with a mockup active part, was designed for arc resistance using nonlinear static finite-element analysis and a specific rupture criterion. It was then tested using an experimental methodology based on injecting pressurized air into the water-filled tank. To adequately reproduce the effects of an arc in oil, the test parameters were determined using explicit dynamic simulations. The transformer tank performed as predicted by the finite-element and explicit dynamic simulations. The energy levels used in the tests here are, to our knowledge, the largest ever reported. This study demonstrates that it is feasible to design a power transformer to safely withstand high-energy low-impedance faults of short duration.