2020/01/03 by Han, Tong, Hill, David J.
#FOS: Electrical engineering #Systems and Control (eess.SY) #electronic engineering #information engineering
paper · doi:10.48550/arxiv.2001.00787
This paper investigates the utilization of transmission switching to improve synchronization performance of low-inertia grids. The synchronization performance of power girds is first measured by the H2 norm of linearized power systems. Laplacian-based bounds and a close-form formulation of the H2-norm synchronization performance metric are derived to reveal the influence of network structure on synchronization performance. Furthermore, a transmission switching approach is developed by analyzing the sensitivity of the H2-norm metric to perturbation of network susceptance. Effectiveness of the proposed approach to improve synchronization performance is demonstrated using the SciGRID network for Germany.