2021/11/23 by Liao, Yicheng, Wu, Heng, Wang, Xiongfei +3
#FOS: Electrical engineering #Systems and Control (eess.SY) #electronic engineering #information engineering
paper · doi:10.48550/arxiv.2111.12013
The stability of multi-vendor, multi-terminal HVDC systems can be analyzed in frequency domain by black-box impedance models using the generalized Nyquist stability criterion. Based on the impedance stability analysis, a multi-level sensitivity analysis approach using frequency-domain sensitivity functions is proposed to identify the root cause of potential instability. Case studies on a four-terminal HVDC system are carried out for stability and sensitivity analysis based on the impedance measurement in PSCAD. The analysis results are finally validated by electromagnetic transient simulations.