Experimental fire tower studies of elevator pressurization systems for smoke control

2019/11/21 by Tamura, G. T., Klote, J. H.
#Bureaux à aires ouvertes #Gestion de la fumée #Open-plan offices [cubicles] #Smoke management #air vents #bouche d'aération #cage d'ascenseur #clapet de ventilation #dampers #elevator shafts #firefighting #handicapped evacuation #mechanical pressurization #pressure control systems #régulateur de fumée #smoke controls #smoke movement

paper · doi:10.4224/40001418

Abstract

Tests were conducted in the experimental fire tower at the National Research Council of Canada to study smoke movement through elevator shafts caused by a large fire and to determine the effectiveness of mechanical pressurization in keeping the elevator shaft and lobbies tenable for evacuation of the handicapped and for use by firefighters. The tests indicated that pressure control is required to cope with loss of pressurization due to open doors. Equations were developed to assist in designing pressure control systems involving either a variable supply air rate with feedback control or relief dampers in the walls of the elevator shaft or lobbies. Tests conducted in the tower indicated that for both methods of pressure control, comparison of measured and calculated values of supply air rates and pressure differences are in good agreement.